One of the best honest power solution supplier in China !
Telecom Charger, Solar charger, Inverter, Lithium battery, Data center products; Industry project.
Telecom Charger, Solar charger, Inverter, Lithium battery, Data center products; Industry project.
PRODUCTS
Telecom Module
-
HUAWEI Inverter Module I23003G1I23003G1
Huawei Inverter Module I23003G1
1. Product Overview
The Huawei I23003G1 is a high-efficiency DC/AC inverter module that converts 48V DC power (from a telecommunication DC power system) into stable 220V/230V AC power. It provides high-performance, uninterrupted AC power for AC equipment in communication sites. The module supports hot-swapping for online replacement, features an intelligent speed-controlled fan, and supports N+1 backup configuration for system reliability .2. Key Features
High Efficiency: Peak efficiency ≥93.5%
Wide DC Input Range: 42V DC – 58V DC
Hot-swappable: Supports online replacement without system shutdown
Parallel Operation: Supports output paralleling for power expansion
Wide Temperature Range: -40℃ to +75℃ operation
Intelligent Fan: Built-in fan with temperature-controlled speed regulation
Comprehensive Protection: Overvoltage, undervoltage, overload, short circuit, overtemperature protection
Remote Management: Supports remote monitoring and management via communication system
3. Technical Specifications
3.1 Input Specifications
Parameter Specification Input Voltage Range 42V DC – 58V DC (Rated: 48V DC / 53.5V DC) Max. Input Current 75A max 3.2 Output Specifications
Parameter Specification Rated Capacity 3000 VA Rated Power 2400W (52V DC – 58V DC input)
2000W (42V DC – 52V DC input)Output Voltage 220V AC / 230V AC (Default: 230V AC)
Adjustable: 200/208/220/230/240V AC via monitoringOutput Frequency 50Hz / 60Hz ±1% Output Power Factor 0.8 Efficiency (Peak) ≥93.5% Current Crest Factor 3:1 Voltage Regulation Precision ±2% Output Protection (Surge) 2KV/4KV 3.3 Overload Capability
Load Condition Duration 105% – 125% (at 2400W rating) > 1 minute > 125% (at 2400W rating) ≤ 1 second 105% – 125% (at 2000W rating) > 10 minutes 125% – 150% (at 2000W rating) > 10 seconds > 150% (at 2000W rating) ≤ 1 second 3.4 Environmental & Mechanical Specifications
Parameter Specification Operating Temperature -40℃ to +75℃ Storage Temperature -40℃ to +75℃ Relative Humidity 5% – 95% RH (Non-condensing) Altitude 0 – 5000 m (Derating required >2000m: -1℃ per 200m) Dimensions (H x W x D) 40.8 mm x 105 mm x 269 mm Weight ≤ 2.2 kg Cooling Forced air cooling (Built-in intelligent fan) Ingress Protection IP20 Audio Noise ≤ 55 dB (sound pressure level) MTBF > 500,000 hours (at 25℃) Insulation Resistance ≥ 10 MΩ 4. Indicator LEDs and Status Descriptions
The module features three status indicators for easy troubleshooting .Indicator Color Status Description Power Indicator Green Steady On DC input present, normal operation Off No DC input or module internal fault Blinking (0.5Hz) DC input present, module in communication query state Blinking (4Hz) DC input present, module loading software Alarm Indicator Yellow Off No protection alarm Steady On Protection alarm: over/under voltage, overtemperature, output short circuit, overload timeout, phase-lock failure Blinking (0.5Hz) External communication failure Fault Indicator Red Off No fault Steady On Internal fault (no output) or module not properly installed 5. Protection Features
DC Input Protection: Overvoltage, undervoltage
AC Output Protection: Overvoltage, undervoltage, overcurrent, overpower, short circuit
Over-temperature Protection
Output Overload Protection
6. Certifications & Standards
The module complies with international standards including :
TUV, CE certified
CB certificate obtained
IEC/EN 62477-1
EN55032 (EMC)
IEC61000-4-2, -3, -4, -5, -6 (Immunity)
RoHS compliant
7. Applications
Telecommunication base stations with AC equipment requirements
DC power systems requiring AC output conversion
Industrial power systems
Sites requiring N+1 redundant inverter configuration
Remote monitoring and management scenarios
8. Important Notes
Output Capacity Derating: Full 3000VA/2400W output is only available when DC input voltage is between 52V and 58V. At lower DC input voltages (42V-52V), the rated output capacity is 2500VA/2000W .
Temperature Derating: Linear derating applies between 50℃ and 75℃ (20% derating at 75℃) .
Altitude Derating: For altitudes between 2000m and 5000m, the maximum operating temperature derates by 1℃ per 200m elevation increase .
The I23003G1 is the newer model that replaces the older I23002G1 (2000VA/1600W). These two models are not interchangeable in system configurations .